Voltage Drop Calculator

Estimate voltage drop and load voltage for single-phase and three-phase circuits.

AEO summary

A voltage drop calculator estimates how much voltage is lost between the power source and the load.

Use this page to estimate voltage drop, drop percentage, and voltage at load for single-phase and three-phase circuits. It is most useful when you need a fast answer about whether conductor size, run length, and current are likely acceptable before detailed design review.

  • Shows how voltage, current, conductor size, material, and distance interact.
  • Helps decide whether a conductor should be upsized to reduce loss.
  • Supports quick checks against common 3% branch-circuit guidance.
Approx. 5.26 mm² • 10.4 kcmil
Voltage Drop
0.0000V
Drop Percentage
0.0000%
Voltage at Load
0.0000V
⚠️ Warning: Voltage drop exceeds the recommended 3% limit for branch circuits. Consider increasing the wire gauge.

How to read the result: voltage drop is the estimated loss across the conductor run, drop percentage shows how significant that loss is, and voltage at load shows the approximate voltage still available to the equipment.

If the percentage is above your target, try a larger conductor, a shorter run, or a different circuit arrangement before finalizing the design.

Frequently Asked Questions

What voltage drop percentage is commonly recommended for branch circuits?

A commonly cited NEC-oriented guideline is to keep branch-circuit voltage drop to 3% or less, with total feeder plus branch-circuit voltage drop often kept to 5% or less.

What inputs does the voltage drop calculator use?

This calculator uses system phase, source voltage, load current, conductor size, conductor material, and one-way distance to estimate voltage drop, percentage drop, and load voltage.

Understanding Voltage Drop in Electrical Circuits

Voltage drop is the reduction in voltage in an electrical circuit between the source and the load. It is caused by the inherent impedance—primarily resistance—of the conductors carrying the current. The National Electrical Code (NEC) Section 210.19(A) Informational Note No. 4 recommends that the total voltage drop for a branch circuit should not exceed 3%, and the combined voltage drop of feeder and branch circuit should not exceed 5%.

Single-Phase vs Three-Phase Calculations

For Single Phase (1φ): Vd = (2 × L × I × R) / 1000 — The factor of 2 accounts for the round-trip distance of current flow through both the hot and neutral conductors.

For Three Phase (3φ): Vd = (1.732 × L × I × R) / 1000 — The square root of 3 (≈1.732) factor accounts for the phase angle differences in a three-phase system, where current flows through multiple conductors with 120° phase separation.

Related Tools