Voltage Drop Calculator

Estimate voltage drop and load voltage for single-phase and three-phase circuits.

Approx. 5.26 mm² • 10.4 kcmil
Voltage Drop
0.0000V
Drop Percentage
0.0000%
Voltage at Load
0.0000V
⚠️ Warning: Voltage drop exceeds the recommended 3% limit for branch circuits. Consider increasing the wire gauge.

Frequently Asked Questions

What voltage drop percentage is commonly recommended for branch circuits?

A commonly cited NEC-oriented guideline is to keep branch-circuit voltage drop to 3% or less, with total feeder plus branch-circuit voltage drop often kept to 5% or less.

What inputs does the voltage drop calculator use?

This calculator uses system phase, source voltage, load current, conductor size, conductor material, and one-way distance to estimate voltage drop, percentage drop, and load voltage.

Understanding Voltage Drop in Electrical Circuits

Voltage drop is the reduction in voltage in an electrical circuit between the source and the load. It is caused by the inherent impedance—primarily resistance—of the conductors carrying the current. The National Electrical Code (NEC) Section 210.19(A) Informational Note No. 4 recommends that the total voltage drop for a branch circuit should not exceed 3%, and the combined voltage drop of feeder and branch circuit should not exceed 5%.

Single-Phase vs Three-Phase Calculations

For Single Phase (1φ): Vd = (2 × L × I × R) / 1000 — The factor of 2 accounts for the round-trip distance of current flow through both the hot and neutral conductors.

For Three Phase (3φ): Vd = (1.732 × L × I × R) / 1000 — The square root of 3 (≈1.732) factor accounts for the phase angle differences in a three-phase system, where current flows through multiple conductors with 120° phase separation.